Electrical practice questions

25 questions from the home inspector exam practice test.

Electrical practice test

10 questions, graded as you go, with the reason for every answer. No sign-up.

What this covers

Sample questions

What is an arc-fault circuit interrupter (AFCI) designed to do?

  1. Detect small leakage currents that could shock a person
  2. Limit the voltage delivered to sensitive electronics
  3. Detect arcing in wiring and shut the circuit off
  4. Switch the house to backup power during an outage
Show the answer

C. Detect arcing in wiring and shut the circuit off

An AFCI recognises the electrical signature of arcing, such as at a damaged cable or loose connection, and opens the circuit before it starts a fire. Detecting leakage current to protect people is what a GFCI does.

Reference: Electrical: AFCI operating principle (NEC 2023 210.12, concept)

In a panel, two branch circuit wires are clamped under the single screw of one breaker that is not designed for two wires. What is this defect called and why does it matter?

  1. A backfeed; the breaker is being fed power from its load side
  2. A bootleg ground; the neutral is now tied to the ground
  3. A double tap; the wires may be loose and can overheat
  4. A split bus; the breaker now feeds two different voltages
Show the answer

C. A double tap; the wires may be loose and can overheat

Most breaker terminals are listed for one conductor. Two wires under one screw may not be clamped evenly, which leads to a loose connection, arcing and heat. Some breakers are specifically designed and marked for two conductors.

Reference: NEC 2023 110.14(A) (terminals for more than one conductor)

What is the largest fuse or breaker that normally protects a 12 AWG copper branch circuit conductor?

  1. 15 amps
  2. 20 amps
  3. 30 amps
  4. 40 amps
Show the answer

B. 20 amps

The small-conductor rule limits 14 AWG copper to 15 amps, 12 AWG to 20 amps and 10 AWG to 30 amps. A 30-amp breaker on 12 AWG wire is over-fusing and lets the wire overheat.

Reference: NEC 2023 240.4(D) (small conductors)